Load switch in the selection of electrical fuse combination of technical problems

(2007-9-23 15:36:49)
Visits

 
    
In recent years, the protection of 10kV distribution transformers and switch control of the selection, as load switching - Fuses and circuit breakers electrical portfolio compared with simple structure, operation maintenance convenience, low cost, reliable operation and advantages, so that combination appliances were widely used.  In actual application, how to choose the right combination of electrical appliances, load switch, fuse and how reasonable matching transformer parameter is related to the combination of electrical appliances can play a role in ensuring safe operation of the system key issue. 
   
   1The combination of three-phase electrical fuses melt melting time-poor, in a three-phase Fuse disconnected after the first phase, the probe moves at the other two possible extinction of Fuse not breaking, and by the formation of the solar system offensive load switch to cut off the fault current phenomenon, the original commitment by the Fuse Breaking tasks transferred to the load switch commitment. Therefore transfer refers to fuse with the current load switched symmetric functions of the three-phase current.  Below that value, the first phase opened by the current Fuse Breaking other two-phase  More than the value, the three-phase current broken only by a fuse.  Transfer current portfolio is in the selection of electrical goods to be an important indicator, if used improperly, can bear the load transfer switch current is not enough, can not afford to take-off two-phase short-circuit current task switch caused the explosion. 
   Load Switches usually divided into general and the frequency of two-to air as insulation medium-gas production and gas-pressure load switch for the general type, SF6 and vacuum switches for frequent load of different load switch, the current transfer targets varied, the general-load switch in the transfer current 1000A 800 ~ about 1,500 frequent-up to 3150A. 
 The different distribution transformer capacity, the corresponding current transfer is not the same, the actual transfer of transformer capacity by the current estimate.  General 800ö10 S9-type distribution transformers for the transfer of current 978A. 
  According to the current definition of the transfer and integration of the load switch-off time and characteristics of load transfer switch to avoid the current maximum short-circuit current, short-circuit current control to the maximum of 70%, and the actual current transfer about 978 x 70% = 685A.The analysis of domestic load switch and fuses on the basis of technical factors, taking into account the discrete products, in accordance with the results of checking the current transfer to the city experience within 800kVA capacity in transformers, air insulation options for the general-load switch, at 800 ~ 1250kVA capacity within the scope of change Pressure for general use vacuum or SF6-insulated frequent load-switching.1250kVA capacity than the transformer requires selection breaker protection and control.  City electrical years from the combination of performance, safety and reliability, in good condition, has not been seen as improper matching incidents. 
   
   2 Two indicators of the current transfer Matching 
   Some load switch with nearly Lai Release set for the trip, with the protection, overload protection adopted at the manner load switch tripping without burning fuse, the fuse only for short circuit protection. Release from Lai-action movements of the relay with a time fuse - Current points of intersection called "transfer of currentThe handover is a current over-current value, below the current transfer current from the Li Release moves to switch off load than when the current transition from Fuse Protection. This transfer of current parameters matching the higher load switches, fuses can be effective in reducing the frequency of movements, which greatly reduces the number of replacement fuse, which has certain technical and economic significance. The vacuum and SF6 load switch, the relatively high current transfer value, and improve the transfer of close to current transfer current, to give full play to such frequent load of the switch-off of a strong advantage. 
   
   3  Three current-limiting fuses Matching 
   The load switch - combined electrical fuse, load switch for normal current or transfer of the current outage, Fuse commitment overload current and short-circuit current of breaking, two electrical appliances breaking capacity cooperate with each other to be completely smooth breaking task, current-limiting fuses matching crucial.  The current-limiting fuse chosen should have a high breaking capacity, the smallest of small-off current, low operating temperature, time - current characteristic curve steep curve of error characteristics. At the same time, meet the aging installed in various forms, suitable size and shape requirements.  It should be noted in the environmental temperature of 40 ° C, with broken power loss shall not exceed 75W. 
  Selection Fuse, Fuse rated current transformer with the capacity to match.  Some people believe that the selection of rated current Fuse will be more security is wrong, it will not only lead to economic waste, but also to fuse the "time - Current Characteristics of" deterioration, reducing the speed protection, the right impact Fuse Breaking protection. In accordance with the IEC standards, the 10 kV system, the relative sizes of transformers, fuses rated current general may table a choice: 
4  Four other issues to be 
   (1) For multi-tie distribution transformer operating system, in the selection of electrical portfolio, with special attention to the current transfer calibration, the calibration calculated as mentioned earlier, if the same for the two models, the distribution transformer capacity parallel running, if transformer secondary side terminals shorted impedance transformer will be at Only a single distribution system changed half the high side so that the largest three-phase short-circuit current to be doubled, may be the current transfer also will have doubled.  Therefore multiple distribution transformer running parallel systems, the use of group 
  A more electrical current transfer should be checked, and the transfer current indicators used to meet the requirements of electrical portfolio. 
 (2), one of the following requirements, the combination of electrical distribution points should Lai Release achieve rapid electrical load switching points gate: 
   1 to set up gas-oil immersed transformer protection. Under normal circumstances, the capacity of 800kVA and above are required to set up the Oil-Gas transformer tripping protection. 
  ② dry-type transformers tripping over-temperature protection. 
   ③ band shell dry-type transformers mistakenly charged the door tripping protection. 
 ④ a remote control and operation requirements. 
   
  5 CONCLUSION 
   In short, the load switch - electrical fuse portfolio selection should be based on actual usage occasions, in accordance with the transformer capacity and operation modes, with various types of load switch the technical parameters and breaking capacity to strike a transfer of current and transfer of current, load switch, and transformer fuses reasonable election Distribution parameters, thereby making the correct combination of electrical options portfolio to ensure safe and reliable operation of electrical appliances. 